Monitoring Pengaruh Pembebanan Terhadap Lifetime Transformator Distribusi 1000 Kva di Hotel Ijen Suites Malang
Monitoring The Effect Of Loading On 1000 Kva Distribution Transformers Lifetime in Hotel Ijen Suites Malang
Distribution transformer is equipment that has an important role in the operation of the electric power system, so this equipment must be maintained in order to have a long lifetime. This study aims to know the effect of loading and ambient temperature on the life loss of distribution transformers. In IEC 354 publication, transformers are basically designed with an ambient temperature of 20 oC. However, transformers in Indonesia operate at an average ambient temperature of 30 oC. Therefore, the load must be adjusted so that the transformer has a normal life loss. The transformer life loss is affected by the winding insulation and the transformer oil. From the results of the study, it was found that the B&D transformer with a capacity of 1000 kVA was loaded by 33.5% to 43% has decreased in daily life loss of 0.3055%, with a relative thermal aging rate between 0,0024 to 0,0044. This shows the value hotspot temperature of the transformer is 45,6289 °C to 50,9383 °C. It can be concluded that this transformer has safe conditions to operate because the value hotspot temperature is still far from its maximum limit value of 98 °C.