Studi Pengaruh Konfigurasi Seri dan Paralel Solar PV Terhadap Penentuan Peralatan Sistem Proteksi di Laboratorium Renewable Energy Politeknik Negeri Malang
Study of the Effect of Solar PV Series and Parallel Configurations on the Determination of Protection System Equipment in the Renewable Energy Laboratory of the State Polytechnic of Malang
PLTS is one of the New Renewable Energy (EBT) generators that use solar power from the sun. This PLTS system does not rule out the possibility of disturbances, whether caused by nature or disturbances due to component malfunctions. In the PLTS system, a protection is needed to secure the components contained in this PLTS system. One of the important protection devices is overcurrent protection devices. Therefore, the importance of the overcurrent protection system needed in a solar photovoltaic module. Protection that functions when there is a surge of current and this overcurrent protection component must have a rating of at least 115% of the short circuit of the solar module. Perform calculations and determine specifications using references from the literature. Testing the tool to determine the performance of the tool that has been determined. Analyze the results obtained after testing the tool whether it functions normally and optimally. The selection of Miniature Circuit Breaker DC (MCB DC) components according to the output current capacity rating of series and parallel PV circuits is Miniature Circuit Breaker DC (MCB DC) of 6 Ampere DC. Miniature Circuit Breaker AC (MCB AC) which is in accordance with the maximum load current capacity rating of the inverter is Miniature Circuit Breaker AC (MCB AC) of 2 Ampere AC. Miniature Circuit Breaker AC (MCB AC) which is in accordance with the load current capacity rating is Miniature Circuit Breaker AC (MCB AC) of 1 Ampere AC. Testing MCB 6 A when hot bimetal flows 10.97 amperes it takes 1 second to trip, when the hot bimetal flows 8.55 amperes, it takes 6 seconds to trip. Cold bimetal flowing with a current of 10.97 amperes takes 3 seconds, but for cold bimetal flowing 8.55 amperes it takes 10 seconds, Testing MCB rating 1 A with a normal load, the current flowing in the AC system is 0.62 amperes without tripping. Testing MCB 1 A towards the load, when hot bimetal flows 3.5 amperes, it takes 1 second to trip, when hot bimetal flows by 1.46 amperes it takes 51 seconds to trip. Cold bimetal flowing with a current of 3.5 amperes takes 6 seconds to trip, but for cold bimetal flowing with a current of 1.46 amperes it takes 1 minute 52 seconds. At the time of testing, all MCBs were in accordance with the standard because they still met the requirements of the type C characteristic curve.