Rancang Bangun Prototipe Automatic Change Over Sistem Double Feeder 20kv Berbasis Microcontroller
Design Of Prototype Automatic Change Over Double Feeder 20kv Based On Microcontroller
The reliable of the electric power system in distributing electrical energy is important to note. In industry, especially industries that have a large scale use medium voltage networks. Electrical energy used in industrial processes as much as possible does not disruption until blackouts because it can cause technical loss and cost up. To reduce this risk can apply 20 kV cubicle with two sources. The transfer process from feeder 1 to feeder 2 or otherwise should occur in a short time and there is no voltage sag. Voltage sag is defined as the voltage drop from its nominal value in a certain time. For Sub system 20kV 1000 milliseconds. So that the speed of the transfer time can be achieved, used an equipment called Automatic Change Overswitch (ACO), which is equipment used to move the main supply to backup source or otherwise. ACO has a fast transfer speed and can be adjusted according to field conditions and needs by relying on a control system that can be a PLC or other microcontroller. This Automatic Change Over prototype focuses on the use of a voltage sensor and is based on a microcontroller using an Arduino Uno type. Arduino as the central controller and receiver of the input signal from the sensor. The voltage measured by the sensor will be the parameter for the relay to work. The parameters are set in the microcontroller program. Two different types of prototypes were made with each different sensor to knowing which both of types of sensors used is better include reliability testing. In trials using two types of sensors, the first used is the ZMPT101B sensor which uses the ADC system, which converts the analog signal to digital to be read by Arduino and the second sensor uses the LM358 voltage comparator circuit. The test is carried out by calculating the theoretical delay time based on the specification data and paying attention to the load conditions during the source transfer process. The test results obtained by the ZMPT101B sensor have a delay of 2119.125 ms while the LM358 sensor is 119.001 ms.