Analisis Uji Performa Generator Sinkron 3 Fasa dan Permanent Magnet Synchronous Generator Hasil dari Modifikasi Motor Induksi 3 Fasa

ANalysis Sync Generator Performance Test 3 Phase and Permanent Magnet Synchronous Generator Result From Modification of 3 Phase Induction Motor

ANANDA PUTRI CHUSNUL CHOTIMAH

This thesis discusses the performance test of 3 Phase Sync Generator and Permanent Magnet Synchronous Generator.The construction and working principle of 3 Phase Sync Generator and Permanent Magnet Synchronous Generator have similarities, but on Permanent Magnet Synchronous Generator uses permanent magnet to generate flux and generate GGL induction, while Synchronous Generator requires excitation current input to produce GGL induction.To know the performance and characteristics of both generators, four tests were conducted, namely: DC Resistance Test, loadless testing, short circuit testing, and testing using variations and types of loads. The parameter generated through DC Resistance testing on PMSG is Ra = 10.2 Ω while in synchronous generator known Ra = 1.82 Ω. Synchronous generator and PMSG when the state of loadlessness and rotor rotation speed is increased then the output voltage generated will be greater and from both generators the percentage increase in output voltage is greatest experienced by PMSG by 29%. Testing using resistive loads on Synchronous Generators and PMSGs can be known that the amount of load given to the generator will affect the amount of voltage generated and in synchronous generators experience a greater decrease in output voltage of 10.46%. Similarly, when testing using inductive loads, the amount of load provided will affect the amount of output voltage produced by generators and synchronous generators experiencing a greater decrease in output voltage than PMSG when given inductive load of 22.27%.The Synchronous Generator's reactive power limit based on the capability curve is 0.405 KVAr to 1.448 KVAr.Pmsg has a reactive power limit based on a capability curve of 0.94 KVAr to -0.94 KVAr.

© 2026 UPA Perpustakaan POLINEMAStatus LayananKebijakan PrivasiSyarat & Ketentuan

v2026.11.20.5 · 33e0fa7