Perancangan Sistem SCADA pada Kontrol Flow dan Pressure Dengan Metode PID

SCADA System Design for Flow and Pressure Control Using the PID Method

HATTA MAHAKIM

Technological development in the world of industrial automation are indispensable, especially in its ability to control and monitor the plant from a safe place. SCADA is one of the suitable system in monitoring and database of plant. In the industrial world many parameters should controlled to maintain the quality of product such as temperature, flow, or pressure. Therefore, it is important for an educational institution to educate their student in the control system in order to get involved into the industrial world. At the design of this SCADA system the operator can configure the PID parameters on the flow and pressure controls. The results of this SCADA experiment were found a PID control of the proper flow for the set point of 80 mL/s with Kp = 198, Ti = 1.2, Td = 0.3. The results of the system response did not find steady state but with the average approaching set point, it was due to inaccurate sensor in the reading with a rise time (Tr) of 6 seconds and a peak time (Tp) of 6 seconds. The PI Parameter of the pressure control on the exact 6 Psi set point is Kp: 5.49, Ti: 2.1. System response generated with these parameters is very good without oscillation and steady state in accordance the set point with a rise time (Tr) of 7 seconds and a peak time (Tp) of 0 seconds, whereas when using the PID control system response is unstable.