Analisis Koordinasi Relai Proteksi Pada Transformator 1 150/20kV Gardu Induk Bumicokro Akibat Uprating Daya dari 50 MVA Menjadi 60 MVA
Analisys of Coordination Protection Relay in Transformer 1 150/20kV Gardu Induk Bumicokro Due to Power Uprating from 50MVA to 60MVA
DENNY KRISMA ANUGRAHITA, RACHMAD BAGUS PAMARDHIKO
Transformer 1 Bumicokro was one of the transformers founded at the Bangil substation. Previously, the transformer had a capacity of 150 / 22kV 50 MVA, due to load growth, an uprating was carried out on the transformer with a new capacity of 60 MVA. Changes in the capacity of the transformer 1 bumicokro resulted in changing the protection relay settings installed on the transformer 1 bumicokro. changes in the capacity of the transformer 1 bumicokro resulted in changing the protection relay settings installed on the transformer bay 1 bumicokro. This is because changes in transformer capacity will change the nominal current value of the transformer which was previously 1314 A with a capacity of 50 MVA and after uprating to 60 MVA, the nominal current becomes 1574 A. Changes in the nominal current of the transformer will also affect the protection relay settings, like OCR (Over Current Relay), GFR (Ground Fault Relay), SBEF (Stand by Earth Fault), Differential Relay and REF (Resistance Earth Fault). The aim of this study is to identify the setting relays, comparison with real circumstances and make simulation from the calculated settings. Based on the calculation that there is no significant difference between the calculations and the real situation. Following the results of the calculated settings in this study, for differential relays the current setting is 2.88 A on the primary side and 3.93 on the secondary side of the transformer with Instant working time settings, for the REF relay the current setting is 0.5 A and 1.1 A with instant working time, for the OCR relay on the primary side, the current setting is 3.5 A with a time setting of 1.19 s, for the OCR relay on the secondary side, the current setting is 4.7 A with a time setting of 1, 07 s, for the GFR relay on the primary neutral side, the current setting is 1.44 A with a time setting of 1.51 s and for the SBEF relay the current setting is 1 A with a working time setting of 8.8 s.