Analisis Power Quality Pada Pusat Perbelanjaan Sarinah Mall Malang

Power Quality Analysis at Sarinah Mall Malang Shopping Center

SYAH ARIEF WAHYU HIDAYATULLAH

Electrical power quality problems are caused by electromagnetic phenomena or phenomena that occur in the electric power system. Quality problems are caused by non-linear loads installed on the electric power distribution system. Power quality problems generally involve harmonics, voltage unbalance, and current unbalance. In this study, an analysis of the quality of electric power at Sarinah Mall Malang includes overvoltage, undervoltage, current unbalance, voltage unbalance, and harmonics. The analysis is done by comparing the calculation results with the standard used. In collecting data in this study using a measuring instrument Web Based Power Quality Meter. The results of the analysis show that there is an overvoltage at Sarinah Mall Malang with the highest voltage reaching 234.49 V and the highest voltage drop of 227.4 V, this value is still below the standard limit. The results of the calculation of the voltage imbalance state that at Sarinah Mall Malang there is a voltage unbalance with the highest percentage of 1.12% and the highest current unbalance value of 7.56%. Based on the IEEE Std 519-1992 standard, the IHDi value that exceeds the standard is on the order of 3, 5, 7, 11, and 15. In accordance with the results of the analysis that has been carried out, it shows that the TDD value exceeds the standard limit, so that at Sarinah Mall it is necessary to plan a harmonic filter. Based on the results of the analysis conducted, the power quality problems that occur at Sarinah Mall Malang are overvoltage, voltage imbalance, and harmonic problems.

© 2026 UPA Perpustakaan POLINEMAStatus LayananKebijakan PrivasiSyarat & Ketentuan

v2026.11.23.3 · f3541dc