Evaluasi Overall Differential Relay (87 TG) sebagai Proteksi Generator dan Generator Transformer Unit GT 2.1 pada PLTGU Blok 2 PT. PJB UP Muara Karang
Evaluation of Overall Differential Relay (87 TG) as Protection for Generator and Generator Transformer Unit GT 2.1 at PLTGU Block 2 PT. PJB UP Muara Karang
Generator and Generator Transformer (Main Transformer) is the main component of the power plant system of PT. PJB UP Muara Karang. Therefore, to protect the main components in the generation process is necessary protection equipment that is capable of protecting both. Overall Differential Relay (87 TG) is a protection relay with its protective zone including the Generator and Generator Transformer. In anticipation of errors of operation that affect the damage, it is necessary to study the evaluation of Overall Differential Relay (87 TG) to be appropriate. Known with the Current Transformer (CT) 1 ratio of 15000/5 A, CT 2 of 15000/5 A and CT 3 of 1500/5 with the old relay setting of I set 1.179 A, slope 30% and new relay setting of I set 1.152 A, slope 30%. Overall Differential Relay (87TG) is able to protect the Generator and Generator Transformer from unbalanced fault that occurs up to 90% of the line impedance value in stator of Generator and Y (wye) connection in Generator Transformer, so for the old setting that is in the field can be said to work as expected. While Overall Differential Relay (87 TG) can work to protect the fault found at the point of F1, but will not work when the fault occurs at the point of F2 due to the outside of its protective zone. Overall Differential Relay (87 TG) protects the Generator Transformer and Generator from short-circuited in the winding, as well as the short-circuited that occurs within its protective zone.