Studi Pengaruh Harmonisa Terhadap Transformator 1 di UPT-PP Politeknik Negeri Malang
Study on The Effect of Harmonic on Transformer 1 at UPT-PP of The State Polytechnic of Malang
The quality of electric power is strongly influenced by the use of certain types of load, such as nonlinear loads and inductive loads. The nonlinear load attracts non-sinusoidal current, even if it was supplied from sinusoidal current. The lack of sinusoidal shape of the current component will send high frequency current components that are injected into the liquid current, known as harmonics. This harmonic current eventually caused many losses, both in terms of engineering, cost and reliability in the electrical system. In terms of cost, for example, the unit of energy used is related to the power component, but with the harmonic current, it will produce additional energy with improper functions. Therefore, one should know how much the impact of harmonics on transformer power loss. Based on the results of the Malang State Polytechnic measurement data, in particular, Transformer 1 has a high harmonic current value of 60.14. %. This will cause transformer power losses, which increase by 68,581 kW, with total transformer losses of 75,188 kW