Analisis Dampak Harmonisa Terhadap Losses Dan Arus Netral Pada Transformator Di PT. Boma Bisma Indra

Analysis Of The Impact Of Harmonics On Losses And Neutral Current On The Transformer In PT. Boma Bisma Indra

BANGUN PRIMEY SETYALAKSANA

Abstract - Loading on E / W transformers at PT. Boma Bisma Indra uses mostly non-linear loads such as welding machines so that reactive and inductive power increases and causes a neutral current in the transformer. In this research, the results of THD measurements were analyzed according to the IEEE 519-1992 standard, losses in the transformer before and after being affected by harmonics, neutral current of the transformer, and derating transformer. The results of the analysis showed that the amount of neutral current due to harmonics is 60.97 A while due to an imbalance of 64.66 A. The losses value before being affected by the harmonics is 23.96 kW, after the harmonics are affected the losses value is 57.77 kW so the total losses are 81.66 kW . Transformer capacity dropped to 1431,85 kVA or 89,4% from initial capacity. Therefore there must be better maintenance of transformers on a regular basis in order to reduce the abnormalities that occur in order to work optimally and can reduce the company's financial loss. Whereas to reduce the value of load imbalance, loading management must be carried out.