Analisis Pengaruh Pengunaan Current Limiter Reactor Sebagai Pembatas Arus Hubung Singkat Di High Voltage Switchgear 6511 20 KV Pada PT. PetroKimia Gresik.

Analysis Of The Effect Of The Current Limiter As The Current-Limiting Short Circuit Current Rating In High Voltage Switchgear (HVS) 6511 20 kV On PT.Petrokimia Gresik

RIZKY SURYA PRADANA

As an industry that plays a role in increasing national food production, electrical energy requirements at PT. Petrokimia Gresik also play a role in the production process, as well as the addition of electrical energy is needed,increasing electrical energy, causing a large short circuit current in the system will continue to increase as well. The ability of circuit breaker (breaking capacity) of equipment such as circuit breaker can not increase except change to a new circuit breaker. If this is done, it will require substantial investment as followed by the replacement of other equipment. Another alternative that can be done to address the magnitude of the short circuit current that occurs is to use the current-limiting equipment that serves to limit the amount of current short circuit, one of them is the use of current-limiting reactors. Besides its ability to limit the short-circuit current. Current limiting reactors have a negative impact such as a voltage drop. The analysis carried out for the evaluation of current-limiting reactors are used. Installation reactors current limiting at HVS 6511 20 kV with a value of 2.4 ohm to lower the value of short-circuit current is quite significant, which was originally 24.15 kA when installed reactors current limiting, its value dropped to 7.73 kA this decline in because the value of impedance of the electrical system of the factory 3A increase in value as a result of adding the reactance of the reactor system. Short-circuit current value is obtained from the calculation and simulation results using ETAP software 12.6.0. Impact mounting reactor current limiters on HVS 6511 20 kV resulted in the increase of reactive power of 0.1 MVAR and fall in value of the active power of 0.1 MW and the falling value of the voltage of 0,26 kV impairment is not fatal in the electrical system in accordance with the standard IEC 60038, and SPLN:72 1987 so installation of current-limiting reactors at 20 kV 6511 HVS can be done at PT. Petrokimia Gresik plant 3A

© 2026 UPA Perpustakaan POLINEMAStatus LayananKebijakan PrivasiSyarat & Ketentuan

v2026.11.23.3 · f3541dc