The source of power energy in Factory III is supplied by 2 generator, that is TG 65 8,5 MW and TG 66 11,5 MW. On December 14th 2015 at unit SA, there was motor 4300 kW 6 kV try to start which is causes sag voltage. A few days later, leakage current happened from winding to body that causes 1 unit of production must separate from the system. Besides 2 generators that have different setting (speed droop and isochronous) must work extra due to the leakage current disorder and discharge 1 that unit of production. According to the calculation of voltage sag and the simulation, when the motor was starting, the voltage was 4400 volt or 73% of 6000 volt. The effect of voltage sag to the motor unit CT is the normal condition torque 3420,28 lb ft be 2381,90 lb ft. For the setting of GFR must use new setting , if there were disturbance the relay will work. From the instances generators TG 65 and TG 66 when conditions normal, disorder on motor 4300 kW 6 kV and the load shedding of unit SA, it has been calculated and simulated, generator TG 66 with setting govenor isochronous that controls the decline in supply to load when there were disturbance on those systems.