AHMAD IQBAL FAIZ

Along with the economic growth and population growth, the need for electricity is also increasing. While the distribution of electrical energy by PLN to the customer must always be maintained quality, efficiency and effectiveness. Load growth can lead to one of the substations of the distribution of the transformer is overloaded so as to reduce the efficiency of electrical distribution. This condition occurs on NA0168 and NA0318 distribution substations that serve household expenses with installed loads 96.62% and 105.52% respectively. This condition has exceeded the 80% loading standard based on SPLN 50: 1997 standard, resulting in an increase in power losses. The solution of the above problems is done installation of substations insert in substation NA0168 and NA0318. To perform a power flow analysis in ETAP 12.6 applications. This application can be used to analyze transformer loading and power losses. The results obtained from this study to determine the benefits of installation insertion transformer, namely the decrease in the percentage of transformer load and decrease in power losses.