Analisis Kinerja Transformator Tiga Kumparan Terhadap Variasi Pembebanan

Analysis of Three Winding Transformer with Variation of Loading

DIYAH MIFTAKHUL JANNAH, FIERLIAN PRIMA RAMADHAN

Transformer that is often found has two windings, namely, primary and secondary windings. In some electric power distribution applications use a three winding transformer namely, primary, secondary and tertiary windings. The use of both types of transformers has advantages and disadvantages. At the writing of this final report aims to determine the function of the tertiary winding connected delta, the characteristics of efficiency and voltage regulation. From the experimental data that has been done, the 2 winding transformer has an efficiency of 82.8% with a voltage regulation of 6.49% and a current harmonics (THDi) of 0.75% and a voltage harmonics (THDv) of 21.5% in a neutral conductor. For transformer 3 windings have an efficiency of 83.3% with a voltage regulation of 6.49% and a current harmonics (THDi) of 0.5% and a voltage harmonics (THDv) of 20% on a neutral conductor. From the analysis conducted, it can be seen that the function of the tertiary winding connected to the delta can reduce the value of harmonics (THDi and THDv). As for the efficiency and voltage regulation values, the 3 winding transformer is better than the 2 winding transformer.

© 2026 UPA Perpustakaan POLINEMAStatus LayananKebijakan PrivasiSyarat & Ketentuan