Tuning Proportional Integral Derivative pada Vapour Absorption Chiller Menggunakan Metode Internal Model Control untuk Menstabilkan Level di Natural Gas Based CS2 PT. South Pacific Viscose, Purwakarta
Tuning Proportional Integral Derivative at Vapour Absorption Chiller Use Internal Model Control Method for Stabilizing Level Controller in Natural Gas Based CS2 Department PT. South Pacific Viscose, Purwakarta
GAGAH ARGA RAYA SAPUTRA, MEYDANA NURRISKY
A vapor absorption chiller (VAC) is a machine to produce chilled water using heat source such as steam (A. Bhatia, 2012). VAC produce condensate from the condensation process that occurs in the generator. Condensate produced will be stored in a vessel and the level will be maintained at set point nominal. Characteristic of controller uses Proportional Integral Derivative (PID) control. Tuning is needed to increase the performance. Tuning is a process to determine parameters of controller for producing the desired result. Tuning can optimized the process system and minimize error between process variable and set point. In this tuning process, Internal Model Control Integrating Process (IMC-IP) method is use. The reason for using IMC-IP method is at the level controller it will not reach a steady state condition when step test is performed. Settling Time, Overshoot, Period of Oscillation and Sum Squared Of Error (SSE) are used to determine and calculate the performance of PID control. Research result is obtained from tuning reaction curve that give the best parameter to transfer function −0,00626 −31,85s e and value of s Pb = 45,45%, τi = 4,35 minutes, and τD = 0.