Fault Identification Of 150 Kv Power Transformer Based On The Duval Pentagon Method Using The Neural Network Method

Julia Agnes Furqonil Iman

This study aims to develop an expert system for power transformer fault identification by creating a multi-layer perceptron (MLP) model. The proposed approach utilizes the Duval Pentagon Method and dissolved gas concentration as input parameters, using MLP to predict the presence of faults in power transformers. The model is specifically designed for fault assessment in power transformers and is trained and tested on generated data 1052 for DPM1 and 1051 for DPM2. The tuning parameters include the number of hidden layers, the activation function type, and the solver. Performance evaluation is based on classification accuracy and confusion matrix. Among the solvers and activation function tested, lbfgs solver and tanh activation function performs the best, achieving an accuracy of 0.981 for DPM1 with 100 hidden layers and an accuracy of 0.991 for DPM2 with 50 hidden layers. Therefore, the model shows that DPM2 is the superior choice. The proposed model is implemented in an expert system, which can assist power utilities and maintenance teams in decision-making processes, leading to more effective and efficient power transformer maintenance.