Fault Identification Of 150kV Power Transformer at UIT JBM Based On IEC 60599-2015

Muhammad Fauzan Sholehudin

Transformer is one of the most expensive equipment that is crucial in the distribution of the electric power system. Transformer performance can be assessed by the reliability of insulating oil through DGA testing. Dissolved Gas Analysis is a method of evaluating transformer status by analyzing transformer oil data samples to get maintenance recommendations. Methane (CH4), ethylene (C2H4), acetylene (C2H2), ethane (C2H6), carbon dioxide (CO2), carbon monoxide (CO), oxygen (O2), hydrogen (H2), and nitrogen (N2) are among the dissolved gases used to monitor transformer conditions. The IEC ratio and Duval triangle are utilized to determine the fault. This study also compares IEC 60599-2015 and IEEE C57.104- 2019 on 8 different 150kV power transformer samples and provides maintenance suggestions based on analytical results comparisons.