Identification Fault of 150 kV Power Transformer Based on IEEE C57.104-2019
In the power system, transformers are crucial electrical equipment that require an insulator or dielectric material, such as insulating oil, to avoid electrical contact between components. DGA test is important for diagnosis and deciding the maintenance of transformers. Duval triangle and roger’s ratio method are DGA identification methods which commonly used to identified fault on the transformer. The data used in this article is from DGA measurement test of transformers UIT JBM – East Java and Bali Transmission Main Unit. The DGA data was analyzed by duval triangle and roger’s ratio method based on IEEE C57.104-2019 standards. The result of fault Identification on six Transformer case study showed LowThermal Fault (T1) <300ºC in Transformer 1 and Transformer 5, Overheating (O) ≤250ºC in Transformer 2 and Transformer 6, and normal condition for Transformer 3 and Transformer 4. The use fault identification to give correct maintenance recommendation action.