Load Imbalance and Harmonics Analysis on The Efficiency of 500kVA Distribution Transformer 1 at UPT-PP Politeknik Negeri Malang
Abstrak
The uneven load distribution and use of non-linear loads on the 500kVA distribution transformer 1 at UPT-PP Politeknik Negeri Malang led to load imbalance and increased harmonics level in the power system. The load imbalance results in power loss through a neutral conductor. The harmonics led to power losses, a heating effect on the transformer, and reduced efficiency. In this study, the load imbalance and harmonics analyses were done based on NEMA MG1 2016 and IEEE 519-2022 standards. The analysis included the percentage of imbalance, THD and TDD levels, power losses due to load imbalance and harmonics, and transformer efficiency. Based on the analysis results, the highest imbalance before load balancing is 20,44% which is reduced to 0,35% after load balancing. The harmonics distortion levels were in accordance with the standard. The lowest efficiency before load balancing is 97,87% which increased to 98,31% after load balancing.