Analisis Perbaikan Power Quality di Bus Sutami

Analisis Perbaikan Power Quality di Bus Sutami

HARIANTO SAPUTRA

Problems regarding voltage drops often occur in electrical energy distribution system especially often occurs in silk bus. One of the causes of the problem occurred due to differences in operation of PLTA Sutami. In order to get good system performance with stable system voltage based on SPLN No. 1: 1995 Section 4 concerning the provision of service voltage variation where the allowable voltage drop is only -10% to + 5%. But the purpose of this thesis is to make the voltage drop not only to ensure that the voltage is in standard condition, but to meet the needs of the customer burden due to demand from PLN Distribui requested directly by the middle voltage customers to reach the farthest point of the load voltage is 20 KV. This thesis is analyzed by Newton-Raphson power flow method in ETAP 12.6 in order to make the voltage condition suitable as desired. Based on the results of the analysis, obtained by raising the operation of the plant into two generating units can raise the voltage of about 2.6 KV, the voltage is initially 137 KV to 139.6 KV. This increase in voltage is similar to the operation of three generating units that increase voltage up to 3.8 KV. Meanwhile, by raising the tap changer step up from position two to position one bus raises tengan up to 9 KV and sutami bus voltage which in normal condition 137 KV rose to 146 KV.